Short Time Current Test | ||||
Sl.NO: | System Voltage | Laboratory Name | Test Parameters | Test Reports Reference |
1 | UPTO 145 KV | CPRI, BHOPAL | 40 KA FOR 3 SECS | S2120338 |
2 | UPTO 245 KV | CPRI, BHOPAL | 50 KA FOR 3 SECS | S2120337 |
3 | UPTO 275 KV | CPRI, Bangalore | 40 KA FOR 3 SECS | S2110676 |
4 | UPTO 275 KV | CESI, ITALY | 31.5 KA FOR 3 SECS | MP-98/024412 |
5 | UPTO 275 KV | CPRI, Bangalore | 63 kA for 1 Sec & Peak 160 kA | CPRIBLRHPLMISC22T0138 |
6 | UPTO 400 KV | ERDA, VADODARA | 50 KA FOR 1 SECS | RP-1718-061859 |
7 | UPTO 500 KV | CPRI, Bangalore | 63 KA FOR 1 SECS | HPL 13201 |
8 | UPTO 500 KV | CPRI, Bangalore | 63 kA for 1 Sec & Peak 160 kA | CPRIBLRHPLMISC22T0142 |
9 | UPTO 500 KV | ERDA, VADODARA | 63 KA FOR 1 SECS | RP-1920-014578 |
10 | UPTO 500 KV | ERDA, VADODARA | 63 KA FOR 1 SECS | RP-2021-034888 |
Temperature Rise Test | ||||
Sl.NO: | System Voltage | Laboratory Name | Test Parameters | Test Reports Reference |
1 | UPTO 145 KV | CPRI, BHOPAL | 1600 AMPS | 2012/STL/498 |
2 | UPTO 245 KV | CPRI, BHOPAL | 4000 AMPS | 2012/STL/497 |
3 | UPTO 275 KV | CPRI, Bangalore | 1250 AMPS | DCCD – 11468 |
4 | UPTO 275 KV | CPRI, Bhopal | 1600 AMPS | 2003/STL/326 |
5 | UPTO 275 KV | CPRI, Bhopal | 1600 Amps | CPRIBPLSTNCMISC2T0272 |
6 | UPTO 400 KV | ERDA, VADODARA | 3150 AMPS 6000 AMPS | RP-1718-056663 |
7 | UPTO 500 KV | CPRI, Bangalore | 4000 AMPS | DCCD - 13598 |
8 | UPTO 500 KV | CPRI, Bhopal | 4000 Amps (100%) | CPRIBPLSTNCMISC2T0271 |
9 | UPTO 500 KV | ERDA, VADODARA | 4000 AMPS | RP-1920-015744 |
10 | UPTO 500 KV | ERDA, VADODARA | 4000 AMPS | RP-1920-015744 |
Resistance Measurement Test | |||
Sl.NO: | System Voltage | Laboratory Name | Test Reports Reference |
1 | UPTO 275 KV | CPRI, Bangalore | DCCD – 11468 |
2 | UPTO 275 KV | CESI, ITALY | MP – 98/024409 |
3 | UPTO 275 KV | CPRI, Bhopal | CPRIBPLSTNCMISC2T0272 |
4 | UPTO 500 KV | CPRI, Bangalore | DCCD - 13598 |
5 | UPTO 500 KV | CPRI, Bhopal | CPRIBPLSTNCMISC2T0271 |
Corona and RIV Test | ||||
Sl.NO: | System Voltage | Laboratory Name | Test Parameters | Test Reports Reference |
1 | UPTO 145 KV | GPRI, Cuddalore | 95 KV (RMS) | GPRI/EN/ACI/049 |
2 | UPTO 245 KV | GPRI, Cuddalore | 156 KV (RMS) | GPRI/EN/ACI/001 |
3 | UPTO 275 KV | CPRI, Bangalore | 190 KV (RMS) | 43/1/2010-HV/8052/ALAPL |
4 | UPTO 275 KV | CESI, ITALY | 190 KV (RMS) | AT-98/029416 |
5 | UPTO 275 KV | CPRI, Hyderabad | RIV Level: 56.2µV at 190kV No Corona observed till 247kV r.m.s | CPRIHYDUHVMISC22T0134 |
6 | UPTO 330 KV | GPRI, Cuddalore | 230 KV (RMS) | GPRI/EN/ACI/033 |
7 | UPTO 400 KV | GPRI, Cuddalore | 266 KV (RMS) | GPRI/EN/ACI/030 |
8 | UPTO 500 KV | CPRI, Bangalore GPRI, Cuddalore GPRI, Cuddalore GPRI, Cuddalore | 350 KV (RMS) | 43/1/2013-HV/1729/ALAPL |
9 | UPTO 500 KV | CPRI, Hyderabad | RIV Level: 68.2µV at 350kV No Corona observed till 455kV r.m.s | CPRIHYDUHVMISC22T0135 |
10 | UPTO 500 KV | GPRI, Cuddalore | 350 KV (RMS) | GPRI/EN/ACI/101 |
11 | UPTO 500 KV | GPRI, Cuddalore | 350 KV (RMS) | GPRI/EN/ACI/125 |
Pullout Strength Test | ||||
Sl.NO: | System Voltage | Laboratory Name | Test Parameters | Test Reports Reference |
1 | UPTO 145 KV | GPRI, Cuddalore | 900 kgs | GPRI/M/ACI/026 GPRI/M/ACI/028 |
2 | UPTO 245 KV | GPRI, Cuddalore | 900 kgs | GPRI/M/ACI/027 |
3 | UPTO 275 KV | CPRI, Bangalore | 900 kgs | VB 1328.T15.0910 |
4 | UPTO 275 KV | CESI, ITALY | 900 kgs | AT – 98/020304 |
5 | UPTO 275 KV | CPRI, Bangalore | No Slip at 900 Kgs | CPRIBLRMEDMISC23T0037 |
6 | UPTO 275 KV | GPRI, Cuddalore | Cantilever Strength | GPRI/MALA/01 GPRI/MALA/02 GPRI/MALA/03 GPRI/MALA/04 |
7 | UPTO 500 KV | CPRI, Bangalore | 900 kgs | VB 2250.T 101.1314 |
8 | UPTO 500 KV | CPRI, Bangalore | No Slip at 900 Kgs | CPRIBLRMEDMISC23T0037 |
Torque Strength Test | ||||
Sl.NO: | System Voltage | Laboratory Name | Test Parameters | Test Reports Reference |
1 | UPTO 145 KV | GPRI, Cuddalore | 150% After Recommended torque | GPRI/M/ACI/026 |
2 | UPTO 245 KV | GPRI, Cuddalore | 150% After Recommended torque | GPRI/M/ACI/027 |
3 | UPTO 275 KV | Regional Testing Centre, | 150% After Recommended torque | 2655/2004-2005 |
4 | UPTO 275 KV | CPRI, Bangalore | Connector should Withstand 150% of the Recommended Torque Value | CPRIBLRMEDMISC23T0036 |
5 | UPTO 500 KV | CPRI, Bangalore | 150% After Recommended torque | VB 2250.T 101.1314 |
6 | UPTO 500 KV | CPRI, Bangalore | Connector should Withstand 150% of the Recommended Torque Value | CPRIBLRMEDMISC23T0036 |